Equipped with its new IGBT rectifier Smart BX series keeps your critical loads protected while its space-saving compact design and front access for maintenance successfully reduce mean time to repair (MTTR).

Parallel configuration up to 8 units per redundancy (N+1) and power increase. Loop connection helps the UPS system to continue the operation when the connection cable is inturrupted.

IGBT based power factor correction technology provides input power factor close to 1 (≥ 0,99). The high input power leads to reduced electricity pay-out, minimizes cable, switchboard, fuse and generator requirements, thus reducing investment cost.

External battery cabinets for different sizes of batteries to provide extended runtimes.Different sizes of 10-40kVA cabinets for larger capacity of internal batteries when long autonomy times are required. 3/1 Phase version is available for 10-30kVA power ratings.
Equipped with its new IGBT rectifier Smart BX -RM is designed for small data center and server rooms. With its rack-mounted design, Smart-BX-RM series keeps your critical loads protected while its space-saving compact design and front access for maintenance successfully reduce mean time to repair (MTTR).
Thanks to the wide variety of accessories and options Smart BX series presents maximum flexibility advantage to users and optimizes total cost of ownership
Smart LV UPS with IGBT based power factor correction technology provides input power factor close to 1 (≥ 0,99). The high input power leads to reduced electricity pay-out, minimizes cable, switchboard, fuse and generator requirements, thus reducing investment cost.
High Efficiency & Low Total Cost of Ownership
Less energy consumption to supply the loads thanks to high efficiency up to 96%.
Reduced energy loss.
Reduced electricity usage and air conditioning requirements.
Reduction in operating cost of UPS.
Low input current total harmonic distortion (THDi) less than 3% helps to avoid the disturbance and expensive harmonic filters.
Small footprint and easy maintenance.
High Output Power Factor 1
Output power factor of 1 (kVA=kW) rate provides up to 25% more active power than a traditional UPS.
Suitable for modern power supply application with unit or capacitive power factor (e.g. new servers generation).
No reduction in active power from 0,9 leading to 0,9 lagging.
Maximum Availability
Parallel configuration up to 8 units per redundancy (N+1) and power increase.
Loop connection helps the UPS system to continue the operation when the connection cable is inturrupted.
| MODEL | Smart BX-S-RM 10 kVA |
|---|---|
| Capacity | 10 kVA |
| Power Watt | 9 kW |
| INPUT | |
| Related Voltage | 380 / 400 / 415 VAC, (3Ph+N+PE) -20% +15% |
| Voltage Range | 208 - 478 VAC |
| Frequency | 50 Hz: 45-55 Hz; 60 Hz: 54-66 Hz (Auto Sensing) |
| Power Factor | ≥0,99 |
| Bypass Frequency Range | 50-60 Hz ±10% |
| Harmonic Distortion | Max. Voltage: 220V: +25% (Optional +10%, +15%, +20%), 230V: +20% (Optional +10%, +15%), 240V: +15% (Optional +10%) Min. Voltage: -45% (Optional -20%, -30%) |
| Generator | Compatible |
| OUTPUT | |
| Voltage Range | 380V / 400V / 415 VAC (3Ph+N+PE) |
| Power Factor | 0.9 |
| Voltage Regulation | ±1% |
| Frequency (AC Mode) | ±1%, ±2% , ±4%, ±5%, ±10% (Optional) |
| Frequency (Battery Mode) | 50-60 ± 0.1 Hz |
| Waveform | Pure Sinewave |
| Crest Factor | 3:1 |
| Harmonic Distortion | ≤2% (Linear Load) ≤5% (Non-Linear Load) |
| Transfer Time | Battery Mode to Inverter Mode 0ms, Inverter to Bypass Mode 0ms |
| Output Dynamic Tolerance | At 100% Load ±5% |
| Overload (AC Mode) | ≤110%: 60min.; ≤125%: 10min.; ≤150%: 1min. ≥150% turn to Bypass Mode Immediately |
| Overload (Battery Mode) | >150% Bypass Mode |
| Parallel Operation | Optional |
| EFFICIENCY | |
| AC Mode | 93,5% |
| Battery Mode | 92,5% |
| ECO Mode | 98% |
| BATTERY | |
| DC Voltage | 240-480 VDC |
| Battery Quantity | (20-40) x 12V 7/9Ah |
| Charge Current | 5A |
| Typical Recharge Time | 8 Hour |
| PROTECTION | |
| Full Protection | Overload, Short Circuit ve Battery Charge-Discharge Protection, RFI/EMI Filtre, IP20 |
| SYSTEM FEATURES | |
| Charge Current | Smart Charging System |
| Over-Temperature | Line Mode: Turn to Bypass; Backup Mode: Shut Down UPS Immediately |
| Intelligent Alarm System | Line Failure, Low Battery, Overload, System Failure |
| LED&LCD Monitor | Line Mode, Battery Mode, Bypass Mode, Battery Low, Overload & UPS Fault |
| ALARMS | |
| Utility Failure | Line Mode, Low Battery, Overload, System Fault |
| Battery Low | Alarm and Shut Down |
| Overload | Overload |
| UPS Fault | System Fault |
| ENVIRONMENTAL | |
| Operation Temperature | 0°C~40°C |
| Storage Temperature | -25°C~55°C |
| Humidity | 0%~90% |
| Altitude | <1500 m |
| Noise Level | <50 dB |
| COMMUNICATION | |
| Communication Interface | USB, RS232, RS485, Parallel Port, Dry Contact, Smart Port, SNMP Card (Optional), Relay Card (Optional) |
| Software | Muser4000, Sofeware |
| Emergency Power Off | Dry Contact (Optional) |
| STANDARDS | |
| Safety | IEC/EN62040-1, IEC/EN60950-1 |
| EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |
| DIMENSIONS &WEIGHT | |
| Dimensions WxDxH (mm) | 440 x 575 x 135 mm |
| Net Weight (kg) | - kg |
IGBT-based power factor correction technology provides an input power factor close to unity (≥ 0.99). The high input power factor helps reduce electricity costs and minimizes cable, switchboard, fuse and generator requirements, thereby reducing investment costs.
Low input current total harmonic distortion (THDi) of less than 3% helps prevent electrical disturbances and reduces the need for expensive harmonic filters.
Compact footprint and easy maintenance.
An input power factor of 0.99 ensures clean, sinusoidal input current.
The high input power factor helps reduce electricity costs and minimizes cable, switchboard, fuse and generator requirements, thereby reducing investment costs.
Parallel configuration of up to 8 units for redundancy (N+1) and increased power capacity.
Loop connection helps maintain UPS operation if a communication cable is interrupted.
Backfeed Protection
Cold Start (Optional)
Advanced Battery Management
Short Circuit and Overload Protection
Parallel Ready
Redundant Power Supply
Power Walk-in for Progressive Rectifier Start-up When Mains Power Is Restored
Battery Temperature Sensor
Static and Manual Bypass Operation
500 Real-Time Event Logs with Detailed Parameters
User-Friendly Multilingual 320 × 240 Graphic Display Providing Operational Information
Monitoring and Shutdown Software
RS232 Serial and RS485 Ports
Modbus RTU (Optional)
2 Communication Slots
Remote Emergency Power Off (Optional)
Remote Display Panel (Optional)
Dry Contact (Optional)
SNMP (Optional)
ProfiBUS (Optional)
Temperature Sensor for External Battery Cabinets to Support Extended Runtimes
External Battery Cabinets Accommodating Different Battery Sizes for Extended Runtimes
Different Cabinet Sizes for 10–40 kVA Models, Allowing Greater Internal Battery Capacity When Longer Autonomy Times Are Required
Three-Phase Input / Single-Phase Output (3/1) Versions Available for 10–30 kVA Power Ratings
Frequency Converter Operating Mode
Isolation Transformers for Flexible Neutral Connections or Galvanic Isolation Between Input and
We stand out by combining decades of engineering excellence with forward-thinking, modular technology. Here is why industry leaders trust us.
Our unique approach to battery storage and frequency converters sets industry standards.
With 40+ years of experience glabally, we bring unparalleled knowledge and skill to every project.
From initial consultation and installation to comprehensive, round-the-clock support services.
Our solutions are trusted internationally, shaping a sustainable global energy future.
With its expertise over 40 years of power protection, EnSmart Power offers a wide range of Line-interactive or Online, Single phase , Tower or Rack-mounted and Online Three phase UPS Power Supply systems with transformer or transformerless from 600VA up to 8MW.
Any power failure can have a devastating impact on mission-critical computers, communications and data, resulting in costly downtime. UPS System is a critical factor to take into account for reliability of today’s data centers.
Avoiding downtime is a top priority in Commercial buildings that systems are operating 24/7/365. Whether it is Hotels, Hospitals, Retail Supermarkets, Public Facilities, Power is crucial for ensuring a safe, healthy environment.
Reliable power supply is crucial to ensure the continuous availability of power and safe operations for all types of manufacturing processes like consumer electronics, pharmaceutical, paper, printing, food & beverage, mining, automotive and etc
A comprehensive range of static frequency converter solutions designed to deliver precise and reliable power conversion for commercial, industrial, marine, aviation, and mission-critical applications. From compact units to high-capacity systems, our converters provide exceptional efficiency, power quality, and scalability for future growth.
Online UPS 3 Phase
• True Three Level Rectifier and Inverter Technology
• Ultra High Energy Efficiency
Online UPS 3 Phase
• IGBT PWM Rectifier & Inverter Technology
• Low Input Current THD (<3%)
• High Input Power Factor (>0.99)
Online UPS 3 Phase
• Built In Inverter Transformer for DC-AC Galvanic Protection
• DSP Vector Control at Input and Output