Service ByPass Panel
25-400 A
Isolation of UPS from Connected Loads for Maintenance with No Loss of Network Availability.
10-15-20 kVA
Online UPS
Equipped with its new IGBT rectifier Smart BX -RM is designed for small data center and server rooms. With its rack-mounted design, Smart-BX-RM series keeps your critical loads protected while its space-saving compact design and front access for maintenance successfully reduce mean time to repair (MTTR).
Thanks to the wide variety of accessories and options Smart BX series presents maximum flexibility advantage to users and optimizes total cost of ownership
3/3 3/1 1/1 Phase convertible RackMounted
IGBT PWM Rectifier & Inverter Technology
Low Input Current THD (<3%)
High Input Power Factor (>0.99)
MODEL | Smart BX-S-RM 10 kVA |
---|---|
Capacity | 10 kVA |
Power Watt | 9 kW |
INPUT | |
Related Voltage | 380 / 400 / 415 VAC, (3Ph+N+PE) -20% +15% |
Voltage Range | 208 - 478 VAC |
Frequency | 50 Hz: 45-55 Hz; 60 Hz: 54-66 Hz (Auto Sensing) |
Power Factor | ≥0,99 |
Bypass Frequency Range | 50-60 Hz ±10% |
Harmonic Distortion | Max. Voltage: 220V: +25% (Optional +10%, +15%, +20%), 230V: +20% (Optional +10%, +15%), 240V: +15% (Optional +10%) Min. Voltage: -45% (Optional -20%, -30%) |
Generator | Compatible |
OUTPUT | |
Voltage Range | 380V / 400V / 415 VAC (3Ph+N+PE) |
Power Factor | 0.9 |
Voltage Regulation | ±1% |
Frequency (AC Mode) | ±1%, ±2% , ±4%, ±5%, ±10% (Optional) |
Frequency (Battery Mode) | 50-60 ± 0.1 Hz |
Waveform | Pure Sinewave |
Crest Factor | 3:1 |
Harmonic Distortion | ≤2% (Linear Load) ≤5% (Non-Linear Load) |
Transfer Time | Battery Mode to Inverter Mode 0ms, Inverter to Bypass Mode 0ms |
Output Dynamic Tolerance | At 100% Load ±5% |
Overload (AC Mode) | ≤110%: 60min.; ≤125%: 10min.; ≤150%: 1min. ≥150% turn to Bypass Mode Immediately |
Overload (Battery Mode) | >150% Bypass Mode |
Parallel Operation | Optional |
EFFICIENCY | |
AC Mode | 93,5% |
Battery Mode | 92,5% |
ECO Mode | 98% |
BATTERY | |
DC Voltage | 240-480 VDC |
Battery Quantity | (20-40) x 12V 7/9Ah |
Charge Current | 5A |
Typical Recharge Time | 8 Hour |
PROTECTION | |
Full Protection | Overload, Short Circuit ve Battery Charge-Discharge Protection, RFI/EMI Filtre, IP20 |
SYSTEM FEATURES | |
Charge Current | Smart Charging System |
Over-Temperature | Line Mode: Turn to Bypass; Backup Mode: Shut Down UPS Immediately |
Intelligent Alarm System | Line Failure, Low Battery, Overload, System Failure |
LED&LCD Monitor | Line Mode, Battery Mode, Bypass Mode, Battery Low, Overload & UPS Fault |
ALARMS | |
Utility Failure | Line Mode, Low Battery, Overload, System Fault |
Battery Low | Alarm and Shut Down |
Overload | Overload |
UPS Fault | System Fault |
ENVIRONMENTAL | |
Operation Temperature | 0°C~40°C |
Storage Temperature | -25°C~55°C |
Humidity | 0%~90% |
Altitude | <1500 m |
Noise Level | <50 dB |
COMMUNICATION | |
Communication Interface | USB, RS232, RS485, Parallel Port, Dry Contact, Smart Port, SNMP Card (Optional), Relay Card (Optional) |
Software | Muser4000, Sofeware |
Emergency Power Off | Dry Contact (Optional) |
STANDARDS | |
Safety | IEC/EN62040-1, IEC/EN60950-1 |
EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |
DIMENSIONS &WEIGHT | |
Dimensions WxDxH (mm) | 440 x 575 x 135 mm |
Net Weight (kg) | - kg |